Skip to main content

NC-PF8-MB

Conventional Fire Panel - PCB - 8 Zone
  • Modern, elegant design
  • Easy removable parts for quick and clean installation
  • Default regional setup modes
  • Normal, head-out & intrinsically safe zone support
  • Supervised alarm notification & fire protection outputs
View all

At a glance

Overview

1X fire control panels offer state of the art architecture in configurations that deliver an uncomplicated solution for small to mid-sized conventional applications. They feature an attractive contemporary design that fits with any decor. The gently curved door front offers a distinctive flair. Operator controls are inset in a striking black lexan.

With support for multiple lines of conventional detectors and accessories, these quick-to-configure systems offer versatility that benefits building owners and installation/maintenance companies alike.

The Panel

The 1X-F8 is a conventional fire alarm control panel. It is supplied in local language with 8 zones that support up to 32 devices per zone, as well as up to 4 supervised relay outputs dedicated to sounder control and fire routing. In addition 2 conventional relay outputs dedicated to common fire and fault conditions, as well as two user configurable inputs for monitoring and control are available.

Options

The panels support 2 types of auxiliary relay boards, one with 4 standard relays, and one with 4 supervised relays. With these boards the panel outputs may be expanded with up to 16 additional outputs.

Approvals & Compliance

The product line carries the following accreditations:

• EN54:2, EN54:4 and CE approved
• CPD certified
• NEN2535, NBNS21-100 and BS5839-1 compliant

• WEEE compliant
• RoHS compliant

Type class conditions: 3K5 of IEC 60721-3-3

Details

  • Modern, elegant design
  • Easy removable parts for quick and clean installation
  • Default regional setup modes
  • Normal, head-out & intrinsically safe zone support
  • Supervised alarm notification & fire protection outputs
  • EN54 compliant potential free fire & fault relays
  • Class change, day/night, remote reset, extended fire routing delay & fire routing inhibit delay facilities
  • Auxiliary 24VDC supply output with reset support
  • Default support for special functions such as: - EN54 compliant user access levels - mixed zones - full front panel diagnostics - one-man walk test - CleanMe™
  • Auxiliary standard & supervised relay output boards
  • Networkable up to 64 zones

Technical specifications

General
Maximum system capacity (device count)
up to 1280
Network size (nodes)
up to 8
Electrical
Power supply type
VAC
Power consumption
4 A @ 24 VDC
Operating voltage
110 VAC @ 50 Hz or 230 VAC @ 50 Hz (+10% -15%)
Cable type: 3 x 1.5 mm² (live, neutral, earth)
Current consumption
3.15 A @ 110/< 1.5 A @ 240 VAC
80 mA (quiescent, no devices) (panel supply)
160 mA (alarm, no devices) (panel supply)
Loop
Maximum loop capacity
8
Zone
Maximum zone capacity
up to 8
Operating voltage
22 VDC (18 to 24 VDC)
Quantity of devices per zone
32 max.
Rating
65 mA (max. Load)
Cable rating
40 ohm (max cable resistance), 500 nF (max cable capacitance)
Input
Input quantity
2
Input type and rating
100 ohm max.
Output
Supervisory voltage
-15 to +28 VDC
Supervised Outputs 4
Load (max) 500 mA
Non Supervised Outputs 2
Load 2 A @ 30 VDC
Standby battery
Capacity
2 x 12 V, 7.2 or 12 Ah (SLA)
Physical
Form factor
Medium
Physical dimensions
440 x 480 x 140 mm (W x H x D)
Net weight
3.9 kg (without battery)
Shipping weight
370 g
Colour
Grey (RAL 7035)
Mounting type
In cabinet
Cable entries
Ø 20 mm - 20 / 2 / 26 (top / bottom / rear)
Environmental
Operating temperature
-5 to +50°C
Storage temperature
-20 to +70°C
Relative humidity
10 to 95% noncondensing
Environment
Indoor
IP rating
IP30
Regulatory
Certification
EN54-13
EN54-2
EN54-4
Standards
EN54-2
EN54-4
EN54-13
Environmental
CPD
WEEE
RoHS
Auxilliary Supply Output
Output voltage 24 VDC (21 to 28 VDC)
Load (max) 250 mA @ 25°C / 195 mA @ 40°C

Downloads

All downloads

Datasheet