FCX-191-000
Fusion Wireless Detector Base w/ Sounder
- Easy to install
- Electronic addressing
- Self-monitoring
- Proven technology
- Eliminates cable installation problems
Related products
At a glance
General
The FCX-191-000 is a wireless detector base with built in sounder (FAD) for use with point type, Fusion wireless detectors. It is ideal for applications where cable interface is difficult to manage or impossible to achieve.
The base connects wirelessly to the Fusion interface unit, which in turn transmits the wireless detector signal to the fire panel hardware loop.
The Range
The Fusion series consists of:
· Optical Smoke Detectors
· Multisensor Smoke Detectors
· A1R Heat Detectors
· CS Heat Detectors
· Sounders in red and white
· Combination Sounder VIDs and VADs
· Manual Call Points
· Interface Modules
· Optical Smoke Detectors
· Multisensor Smoke Detectors
· A1R Heat Detectors
· CS Heat Detectors
· Sounders in red and white
· Combination Sounder VIDs and VADs
· Manual Call Points
· Interface Modules
Operating Principle
Wireless devices are often installed in buildings where wiring presents a challenge because the fabric of the building or its design is negatively affected by the use of cables. It could also be difficult to introduce cable runs into heritage buildings. It is for these architecturally sensitive buildings that the Fusion series was developed.
Every Fusion device is assigned an address from is base. This address is converted by the Fusion wireless loop interface to a device address similar to a wired device connected directly to the loop wiring.
Details
- Easy to install
- Electronic addressing
- Self-monitoring
- Proven technology
- Eliminates cable installation problems
- Uses 868 MHz radio channels
Technical specifications
| General | ||
|---|---|---|
| Wireless frequency |
868 MHz
|
|
| Compatibility |
Fusion gateway FCX-532-001
|
|
| Electrical | ||
|---|---|---|
| Power supply type |
Batteries
|
|
| Batteries |
3x AA Alkaline (Panasonic LR6AD Powerline / Varta 4006 Industrial)
3x C Alkaline (Panasonic LR14AD Powerline / Varta 4014 Industrial)
|
|
| Operating voltage |
3.5 to 4.5 VDC
|
|
| Current consumption |
0.2 to 300 mA
|
|
| Output transmitter power |
0 to 25 mW
|
|
| Sounder | ||
|---|---|---|
| Output level |
< 87 dB(A) @ 1 m
|
|
| Output level adjustment |
13 dB
|
|
| Frequency |
Selectable
|
|
| Selectable tones |
4
|
|
| No. of stages |
2
|
|
| Physical | ||
|---|---|---|
| Physical dimensions |
146 x 53 mm (Ø x d)
|
|
| Colour |
White
|
|
| Mounting type |
Ceiling mount
|
|
| Mounting position |
Ceiling
|
|
| Environmental | ||
|---|---|---|
| Vandal proof |
No
|
|
| Operating temperature |
-10°C to 55°C
|
|
| Storage temperature |
5°C to 30°C
|
|
| Relative humidity |
< 95% non-condensing
|
|
| Environment |
Indoor
|
|
| IP rating |
IP23
|
|
| Regulatory | ||
|---|---|---|
| Compliancy |
CE
REACH
RED (2014/53/EU)
RoHS 2
WEEE
|
|
| Certification |
BOSEC
CPR
|
|
| Standards |
EN54-3
EN54-13
|
|
Downloads
All downloadsDatasheet
Installation sheet
Certificates
If available, the downloads of the Certificates, Software & Firmware and Media are displayed in their default language.